Variateur de fréquence moyenne tension pour ventilateur aspirant de 300MW dans une centrale au charbon
Variateur de fréquence moyenne tension pour ventilateur aspirant de 300MW dans une centrale au charbon
2010-1-4 14:30:42
Résumé : cette page vous présente les principes du variateur de fréquence VFD et sa mise en service sur place, analyse les effets d’économie d’énergie et donnent des références pour comprendre les opérations du variateur de fréquence VFD.
Mots clés : ventilateur aspirant, variateur de fréquence moyenne tension (VFD), contrôle.
1. Introduction
Guodian Xuanwei Power Generating Co., Ltd locates in north-east of Yunnan province with elevation 1960m. Capacity is 4×300MW. Design rating of 7# is 300MW. Furnace is equipped with two axial flow ID fans AN31e6(u19-10). Rated flow is 321.4m3/h. Total pressure is 5452Pa. Shaft power is 2104kW. Motor model is YKK800-8-W. Rated power is 2500kW. Rated voltage is 6kV. Rated current is 293A. Power factor is 0.86. Rated speed is 746r/min. Flow is adjusted by changing angel of fixed blade.
According to requirement of power grid, power generation load usually adjusts in 50%~100% of rated load. With output power of generator changing, relevant equipments of furnace system also adjust with load changing. Air output and air input of furnace change. ID fan is adjusted by changing angle of blade. Despite this adjustment mode has energy saving effect compared with damper control, there is still much throttle loss. Especially during operation of low load, much output power of motor wastes on damper. Secondary, fixed blade adjustment action is slow, causing lag of load adjustment response. During starting, start current is 5~8 times of rated current. Big start current brings big impact on motor and cable, affecting stability of power system. In the mean time, strong impact torque and current shorten lifetime of motor and other equipments. Lots of practises prove that changing motor speed by VFD can solve above problems and meet technics requirement of different loads.
2. VFD operation mode and control logic
Electrical system is ‘one drive one’ mode (dashed line parts is the added).
Medium voltage VFD can switch operation mode according to need. For example: mode of one runs in variable frequency and the other runs in direct on line, and mode of the both run in direct on line. The disadvantage is that during switching, load needs to be adjusted. After lowering load, stop 1# (or 2#) ID fan, then switch the operation mode. In normal state, two ID fans run in variable frequency.
Medium voltage VFD has local control and remote control. In remote control, speed signal from DCS trails VFD speed and makes feedback. In local control, remote control is invalid.
There is auto and manual modes when VFD is controlled by DCS. In manual state, personnel controls VFD speed by changing in interface to realize negative pressure adjustment.
(1) Allowable conditions of starting VFD on ID fan
Precondition of VFD start-up is that medium voltage switch of motor must close, that is, start feedback is 1. Original conditions of fan start preserve as allowable conditions of VFD start. Ready signal from VFD is another start condition.
During VFD commissioning (regardless in local control or remote control), we find minimum frequency can not set less than 15Hz, otherwise it causes overcurrent of power cell of VFD. VFD trips off. So when motor starts, minimum frequency of VFD can not be set less than 15Hz.
Following conditions must be abided when VFDs of 1# and 2# ID fan start:
(1) Start feedback of medium voltage is 1.
(2) Ready from PLC of VFD is 1.
(3) Output of given speed of VFD is not less than 30%.
3.Trip off protection of VFD
After VFD of single side fan trip off, FD fan of the side should link stop.
Medium voltage switches link stop after 1# and 2# VFDs, so preserve original circuit of cascading trip unchangeable.
Safe operation of furnace is fundamental guarantee of plant power. Despite VFD is reliable, once there is problem during operation, safe operation of furnace must be guaranteed. So switch of “line frequency---variable frequency” is needed. Once one VFD of fan is broken and can not recover in short time, system turns to blade adjustment automatically. In this case, stop one variable frequency system and the other ID fan system runs in variable frequency. At the moment, furnace load should keep at about 180MW.
4. Economy estimation
4.1 Obvious effect of energy saving effect
Following data is comparison data of 1#, 2# ID fan with VFD.
Time (October 2005) | Furnace load (MW) | Variable frequency | Direct on line | Comparison (%) | ||
#1 ID fan | #2 ID fan | #1 ID fan | #2 ID fan | |||
Power consumption(kW·h) | Power consumption(kW·h) | Power consumption(kW·h) | Power consumption(kW·h) | |||
20 | 20.35 | 10332 | 11340 | 19908 | 19656 | 45.2 |
21 | 20.32 | 10836 | 11592 | 19908 | 19656 | 43.3 |
22 | 22.02 | 13104 | 13608 | 22428 | 21924 | 39.7 |
23 | 20.32 | 10080 | 10584 | 19908 | 19656 | 47.7 |
Yearly average | 43.9 |
From above table, in the case of same load, daily consumption of two ID fans is 40761 kW·h in direct on line and 22869kW·h in variable frequency. Power saved is 17892kW·h, power saving rate is 43.8%.
4.2 Energy saving calculation
Yearly work time: 7200h
Compared with blade adjustment, VFD adjustment on ID fans can save 5367600kW·h every year. Power price is 0.2553 yuan/kW·h. Cost saved is 5367600kW·h×0.2553 yuan/kW·h=1370348.28yuan (USD 201521)
5. Concluding remarks
Adopting medium voltage variable frequency technology reforms equipment of high power consumption, which not only reduces power consumption and coal consumption, but also plays active part on equipments safety and reliable operation.