Cas de reconstruction avec variateur de fréquence moyenne tension en application thermale

Cas de reconstruction avec variateur de fréquence moyenne tension en application thermale
2010-1-4 12:18:38

I. Situation générale
La centrale thermique de Hegang se situe dans la ville du charbon --- Hegang, dans la province du Heilongjiang, appartenant aux bureaux d’exploitation minière. La centrale est dotée de quatre machines et 6 chaudières, y compris deux générateurs 50MW et deux générateurs 25MW, 4 chaudières 75t et deux chaudières 220t. Les chaudières 5# et 6# sont de 220t. A présent, la chaudière 7# (220t) est en construction.

In addition to supplying power to northeast power grid, the plant also provides heat to Hegang area. ID fan and FD fan of 220t boiler work in direct on line for long term. Air flow is adjusted by damper of ID fan and FD fan to maintain boiler negative pressure. Damper opening is usually 40%. In this way, much energy is wasted on damper.

In summer, only one 220t boiler can meet load requirement. In winter, two 220t boilers usually work due to heat providing. Water feeding system is “one work one standby”. When two boilers run simultaneously, flow and pressure of pump can meet requirement. When one boiler works, outlet pressure of pump is 15Mpa. But pressure demand is only 12.5Mpa. So high outlet pressure needs to be adjusted. Because pump is driven by motor of costant speed, water flow and pressure can be controlled just by valve of boiler. This method has inferior economic benefit, furthermore, high pressure endangers safe operation of pipeline.

In order to solve above problems fully, the plant decided to reconstruct for four fans of 6# boiler and water feeding pump. By adjusting motor speed realizes flow and pressure adjustment to improve technics and save energy.

II. Speed adjustment selection

There are several kinds of speed adjustment modes: cascaded speed adjustment, hydraulic coupling and variable frequency

Cascaded speed adjustment: it can recover slip power, so adjustment efficiency is high. But it is not applicable to squirrel cage asynchronous motor. It can not realize soft start and start is very complicated. Adjustment range is limited. Response is slow, not easy to realize close loop control. Power factor and efficiency is low and lowers sharply with speed down. It is difficult to realize cooperation with PLC and DCS. It is not advantageous to improve automatization level and optimize control. In the meantime, because control device is quite complicated, with serious harmonic pollution to power grid, its application is limited.

Hydraulic coupling speed adjustment: adjustment efficiency is low and adjustment range is limited. High speed slippage is about5%~10%. Slip difference loss is big in low speed. The max can reach to 15% of rated power. Efficiency is quite low during low speed range. Low precision, inferior linearity, slow response, big start current, big dimension. It has to be installed between equipment and motor, not applicable to reconstruction. It can implement soft start. When hydraulic coupling is broken, switching to direct on line is infeasible. Maintenance is complicated with much cost. It can not meet demand of high automatization level.

Medium voltage variable frequency adjustment: it adopts advanced power and electronic technology, computer control technology and communication technology. So it has advantages over other adjustment modes.

a.       VFD has LCD interface and touch screen panel which can show voltage, current, frequency, speed at any time. Personnel can observe motor state at any time.

b.      High frequency resolution and adjustment precision meet technics requirement completely.

c.       VFD has universal external ports which can connect to PLC and control machine, and also can connect to original control circuit, composing close loop system, such as data exchange and linkage with original DCS.

d.      VFD has local control and remote control through internet.

e.       VFD has power protection and electric protection which ensure VFD and motor reliable during normal operation and failure.

f.       Motor can realize soft start/stop. Start current is smaller than rated current of motor. Start time can be adjusted continuously, reducing affection on power grid.

g.      VFD reduces wear and tear on auxiliary components, prolongs equipment lifetime and heightens production efficiency.

So the plant select the most advanced adjustment mode---variable frequency adjustment. By evaluating numerous VFD manufacturers, the plant decided to use Leader&Harvest drive. Leader&Harvest VFD has following advantages:

a.       Leader Harvest takes the biggest market share in China. System runs reliably.

b.      It has perfect HMI.

c.       It has distinct technology predominance at reliability and safety.

d.      Inside PLC changes control logic easily, applicable to site need.

III. System scheme

According to actual state, “one drive one” (see following figure) is adopted.

This is typical scheme of manual bypass. It is composed of three medium voltage isolators QS1, QS2 and QS3 (QF is medium voltage switch). QS2 and QS3 interlock in mechanism and they can not close simultaneously. During variable frequency operation, QS1 and QS2 closeQS3 opensin direct on line state, QS3 closesQS1 and QS2 open. There is obvious power off points for VFD maintenance. System can switch load to direct on line manually.

III. Electrical scheme


 

IV. Construction implementation

Model

Rated voltage

Rated current

quantity

ID fan motor

Y4005-6

6KV

43A

2

VFD

HARSVERT-A06/045

6KV

45A

2

 

Model

Rated voltage

Rated current

quantity

FD fan motor

Y4003-6

6KV

34.3A

2

VFD

HARSVERT-A06/035

6KV

35A

2

 

Model

Rated voltage

Rated current

quantity

ID fan motor

YK2300-2/990

6KV

260A

1

VFD

HARSVERT-A06/270

6KV

270A

1

 

Above VFDs arrived site on 19 th August, 2005. As of 1 October, all installation and commissioning finished and VFDs put into service. Total period is a month.

We equip an upper PC which monitors four VFDs in boiler control room. Modify original control circuit of medium voltage switch. Take a couple of normally open contacts from VFD controller to seal in off circuit of medium voltage switch. This node is defined as “permissible close”. When VFD is supplied control power and self checks normally, this node closes. Supply medium voltage power to VFD through original circuit. Take a couple of normally open contacts from VFD controller to parallel in off circuit of medium voltage switch. This node is defined as “emergency off”. When VFD is serious failure during operation, VFD stops automatically, meanwhile, the node closes, medium voltage switch trips. In addition to above modification for medium voltage switch, before start VFD, we cut off original differential protection of motor. If motor needs to switch to direct on line, the protection is valid.

VFD is installed beside pump. Upper PC is installed in pump control room. Make similar modification for medium voltage switch to meet VFD operation requirement.

V. Energy saving effect

Four VFDs of fans have been running normally since they put into service. Because 6# boiler does not adopt DCS control, installation space of boiler control panel is limited. VFD does not use hard wire to implement remote control, but by an upper PC. Because upper PC can not be installed right ahead of fireman, it is difficult to ensure operation in time. So damper is still needed when VFDs work. That is, according to load state, adjust VFD to lower frequency by upper PC (usually at 40Hz). Damper opening is about 80%. When air flow needs fine adjustment, personnel adjusts damper to ensure timely adjustment.

VFD of pump has been running stably since it put into service. During single 6# or 7# pump operation, pump is controlled by VFD. All valves are full open. In winter, 6# and 7# boilers work together. Single pump should run in full load to meet load demand. So VFD exits and motor runs in direct on line. After 7# boiler put into service, two pumps work together. One works in direct on line and the other works in variable frequency. Variable frequency pump supplements water feeding.

Please see following data

Name

Capacity (KW)

No

Daily power consumption without VFD KWH

Valve opening %

Daily power consumption with VFD KWH

Yearly energy saved

KWH

yearly cost saved

ID fan motor

355

2

15980

38

8200

2839000

1164000

FD fan motor

280

2

7980

45

5200

1014000

416000

Total

635

4

23960

13400

3853000

1580000

Note: 6# boiler works for 10 months every year.

10/12=0.833, yearly cost saved: 1580000×0.833=1310000 yuan (USD 192647)

VI. Concluding remarks

From operation state of several months, Leader&Harvest VFD has good performance and high reliability. Energy saving is obvious. It meets requirement of continuous production, reaches purpose of energy saving and technics improving.

At present, the plant is purchasing eight VFDs again from Leader&Harvest for reconstruction on 5# and 7# boilers. The VFDs are producing in factory now and they will apply successfully in future.

 

 