Application de la technologie de variation de fréquence moyenne tension dans le ventilateur 4# de la compagnie pétrolière Jinxi

Application de la technologie de variation de fréquence moyenne tension dans le ventilateur 4# de la compagnie pétrolière Jinxi
2010-1-4 12:31:44
Résumé : cet article expose la reconstruction pour économie d’énergie du ventilateur aspirant et du ventilateur soufflant de la chaudière 4# de
China Petrolum Jinxi Oil Industry Company et introduit le but de la reconstruction, les schémas, l’implémentation et le principe. Il analyse les effets de la reconstruction, plus spécialement les effets économiques et illustre la signification de cette reconstruction. L’ajustement de fréquence variable est un moyen de gestion efficace pour l’économie d’énergie.
Mots clés : fréquence variable, reconstruction, économie d’énergie, bénéfices accrus.

 

1.      Preface

The plant has three 75t boilers, three 220t boilers. 1#, 2# and 3# boilers are 75t. 4#, 5#, and 6# boilers are 220t. Six boilers all equip ID fan , FD fan and SA fan. The motors of fans are designed as per max load. But boilers run in max load in very short time and they run at 66% load mostly. So actual air flow of boiler demand is not max flow but variable flow which varies with load changing. In order to meet air flow requirement, we use conventional damper adjustment. This way can change air flow but can not change motor speed as well as save energy, causing much energy waste and cost rising.

2. Reconstruction purpose

In order to lower production cost and power consumption, variable frequency technology should be adopted. By utilizing low voltage VFD, the plant has gained considerable energy saving effect and maintenance experience. With maturity of medium voltage variable frequency drive, we utilize this technology outcome to medium voltage motor. We reformed for three fans of 4# boiler in May, 2006.

Parameters of fans

Fan

Motor model

Rated voltage

Rated current

Rated power

Power factor

Rated speed

PA fan

YFKK5004-4

6000V

131A

1120kW

0.85

1490r/min

SA fan

YFKK5001-4

6000V

94A

800kW

0.85

1490r/min

1# ID fan

YFKK4505-6W

6000V

61A

500kW

0.85

990r/min

 

3. Reconstruction scheme

3.1 VFD selection

After comparing and analysing, the plant selected Leader&Harvest VFD eventually.

3.2 Main circuit

We decided to adopt “one drive one” scheme due to importance of fan. That is, one VFD drives one motor of fan. In order to improve reliability and safety, we add bypass circuit. Please see the figure.



 

QF is vacuum breaker. QS1, QS2 and QS3 are medium voltage isolator. Medium voltage VFD is between QS1 and QS2. QS3 is bypass switch. When motor needs to run in variable frequency, open QS3 and close QS1,QS2, then close QF. When motor needs to run in direct on line, open QS1, QS2, close QS3 and then close QF. In this way, motor can run in direct on line during VFD downtime or maintenance.

Above scheme is typical manual scheme. QS2 and QS3 interlock in mechanism and they can not close simultaneously.

In order to realize fault VFD protection, VFD sends trip command when it faults seriously and link trips medium voltage breaker to make VFD off power. In the meantime, three switches interlock  electrically with QF. Only when breaker is off, can personnel operate switch, which ensures safety.

3.3 Control scheme

According to actual state, we adopt three control schemes. They are DCS close loop control, DCS open loop control and local control.

3.4 Cooling scheme

Principle of VFD is to rectify AC to DC and invert DC to AC. During this course, electric components emit heat (2%). The heat causes equipment temperature up and damages equipment. In order to ensure stable work of VFD, the heat must be dissipated outside. So cooling scheme is very important. After researching carefully, we adopt the most effective and easiest scheme---air cooling. Install air duct on top of VFD. The duct discharges the heat outside. The scheme only needs a duct without other device, so it is simple and reliable with few failure factor. Make full load test at 40. Max temperature of VFD reaches to 68. Compared with max design temperature-rising, the result is ideal.

4. Reconstruction effect

4.1 Technics effect after reconstruction

After reconstruction, damper opening is 100%, which reduces resistance loss a lot. Because motor runs in variable frequency, fixed resonance frequency is difficult to be line with operation frequency, thereby resonance can be avoided. So problem of pipeline breakage is solved naturally. This is also an unexpected benefit.

4.2 Impact on power grid

If motor starts in direct on line, start current is 7~8 times of rated current. Big current increases electrical force and creates heat, which shortens motor lifetime. In variable frequency system, motor realizes soft start. Motor can start at zero speed and accelerates to operation current gradually. VFD drives load in V/f control or vector control without impact on power gird.

4.3 Maintenance labour after reconstruction

After reconstruction, motor usually runs in 30Hz~40Hz. Compared with line frequency 50Hz, fan speed lowers. In addition, slow accelerating prolongs equipment lifetime. Damper lifetime is also prolonged. Maintenance labour reduces and maintenance cost reduces too.

4.4 Energy saving effect

Please see following data:

 

Steam flow T/H

PA fan current

SA fan current

ID fan current

Total current difference(A)

Total

Power

difference

Before

(A)

After

(A)

Difference

(kW)

Before

(A)

After

(A)

Difference

(kW)

Before

(A)

After

(A)

Difference

(kW)

140

123

50.1

610.5

77

30.3

393.5

50

18.4

269.0

151.2

1273.0

145

123

50.6

605.2

77

30.8

388.2

50

19.1

261.6

149.5

1255.0

150

124

53.7

581.7

78

31.4

391.1

51

20.1

260.3

146.8

1233.1

155

124

55.1

566.9

79

32.8

385.6

52

21.6

253.7

145.5

1206.1

160

125

60.2

522.2

80

35.1

370.5

52

27.4

192.3

133.3

1085.0

165

125

60.9

514.8

82

36

379.5

52

28.9

176.4

133.2

1070.7

170

126

61.1

521.9

82

37.5

363.6

52

34.1

121.4

127.3

1006.9

180

126

61.1

521.9

82

38.3

355.2

52

38.2

78.0

122.4

955.1

190

129

62

540.2

82

39

347.8

52

43

27.2

119

915.2

200

131

62

558.8

82

39.7

340.3

52

45

6.0

118.3

905.1

Note: power factor is 0.85 before reconstruction and 0.97 after reconstruction.


From above data, during operation from 140t to 200t, we see energy saved reduces with load increasing and increases with load decreasing.
 Boiler works in 140t~150t for about 8 months, in 200t just for 2 months, in 180t for 1 month, maintenance for 1 month. Power consumtion of three fans of 4# boiler is about 18631338.7kWh before reconstruction and 9411516.9kWh after reconstruction. Yearly power saved is 9219821.9 kWh, energy saving rate is 49.5%. that is to say, we can approach production task by 50.5% of power consumption before. Power price is 0.45yuan/kWh, yearly cost saved is 4148919.8yuan(USD610135).

The investment is recovered within the year.

5. Concluding remarks

The reconstruction of 4# boiler was an improtant project in 2006. The project is specific measure of transferring from extensive management to saving management, is a great stride on energy saving. Technics effect and energy saving effect inspire positivity of staff. In the mean time, it indicates enormous potential of energy saving.

 

Produits relatifs
Commentaires
Autres Produits
Envoyer un message
Envoyer un message